Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 16, 2019, 11:36 AM
  • 02 2319_02 1817 _10162019_034945.mp4

Date
10/16/2019
W/O
792797
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00236
PipeID
P08501
Time
4:36 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6967
Sewer Name
02 ATLANTIC AVENUE RELIEF TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_792797_TV02017_OCT2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 2319
Downstream MH
02 1817
Dir. of Survey
Downstream
Length Surveyed
331.6 ft.
Total Length
331.6 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
325
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
326
Pipe schematic from manhole 02 2319 to 02 1817
MH: 02 2319MH: 02 1817downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 23190 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. MGO - General Observation - MAG COAT THROUGHOUT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.4 ft. VC - Vermin Cockroach328 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish331.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1817

Observation photos (2)

  • General Observation - MAG COAT THROUGHOUT

    2 ft. - General Observation - MAG COAT THROUGHOUT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
2MGOMAG COAT THROUGHOUT
328SSS
331.6AMH02 1817
0AMH02 2319
2SSS
0MWL
2SAP
328.6SAP
0MWM
11.4VC

Properties (6)

additional_info
SC378594
custom_field_two
2
customer
LACSD
datetime
2019-10-16T04:36:31-07:00
documentation
PRO PIPE
is_lateral_inspection
false