Wastewater/Activity/PacpInspection/1.0Nov 13, 2019, 08:44 AM
18 0205_18 0204_11132019_025306.mp4
Date
11/13/2019
W/O
0801678
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00695
PipeID
P14030
Time
12:44 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
—
Pre-Cleaning
Heavy Cleaning
Media Label
H1308
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Maintenance Related
Project
20191107MDM_ORR_AND_DAY_ROAD_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
18 0205
Downstream MH
18 0204
Dir. of Survey
Downstream
Length Surveyed
399.2 ft.
Total Length
399.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
5141
O&M Rating
16
Overall Index
3
Overall Quick
—
Overall Rating
16
Pipe schematic from manhole 18 0205 to 18 0204
Observation photos (3)
2 ft. - Deposits Settled Other, 40 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: YES, Start - DEBRIE UNDER FLOW
20.8 ft. - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - DEBRIE UNDER FLOW SPORATIC
107.2 ft. - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - DEBRIE UNDER FLOW SPORATIC