Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2019, 08:30 AM
  • 15 0775_15 0774_1182019_004103.mp4

Date
11/08/2019
W/O
0793083
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12976
Time
12:30 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1303R
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Maintenance Related
Project
20191108MDM_ARACADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0774
Downstream MH
15 0775
Dir. of Survey
Upstream
Length Surveyed
385.7 ft.
Total Length
385.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3123
O&M Rating
11
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 15 0774 to 15 0775
MH: 15 0774MH: 15 0775upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:25AM38.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped41.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - CAPPED111.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped116.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped192.8 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS200.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active234.5 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR - 3%239.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped241.4 ft. RMC - Roots Medium Connection, from 12 to 04 o'clock, 30 %, within 8 inches of joint: YES241.4 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open - 100% ROOTS250.1 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR - 4%287.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped290.9 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open-100% ROOTS385.7 ft. MGO - General Observation - MH CONN 9:00 ACTIVE385.7 ft. MGO - General Observation - MH CONN 3:00 ACTIVE385.7 ft. MWM - Water Mark, 30 %of cross sectional area385.7 ft. MWL - Water Level, 15 %of cross sectional area385.7 ft. AMH - Downstream Manhole, Survey Begins - 12:40AM

Observation photos (1)

  • Roots Medium Connection, from 12 to 04 o'clock, 30 %, within 8 inches of joint: YES

    144.3 ft. - Roots Medium Connection, from 12 to 04 o'clock, 30 %, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
144.3RMC
135.6RFJ4%
344.4TFCCAPPED
192.9TFDOpen-90% ROOTS
144.3TFDOpen - 100% ROOTS
151.2RFJ3%
0MGOMH CONN 9:00 ACTIVE
0MGOMH CONN 3:00 ACTIVE
94.8TFDOpen-100% ROOTS
97.8TFCCapped
185.2TFActive
268.8TFCCapped
274.2TFCapped
0MWM
0MWL
347.1TFCCapped
146.4TFCCapped
0AMH12:40AM
385.7AMH1:25AM

Properties (5)

additional_info
POST ROOT EVALUATION ONLY
customer
LACSD
datetime
2019-11-08T00:30:07-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false