Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2019, 10:40 AM
  • B 0477_B 0476_1182019_033706.mp4

Date
11/08/2019
W/O
0798588
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00094
PipeID
P09002
Time
2:40 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1304R
Sewer Name
B JOINT OUTFALL B - UNIT 5D
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
06
Purpose
Maintenance Related
Project
20191108MDM_JOINT_OUTFALL_B_UNIT_5D
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
B 0476
Downstream MH
B 0477
Dir. of Survey
Upstream
Length Surveyed
265 ft.
Total Length
265 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4135
O&M Rating
24
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole B 0476 to B 0477
MH: B 0476MH: B 0477upstream0 ft. AMH - Upstream Manhole, Survey Ends - 4:05AM25.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped28.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped34.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open43.8 ft. RMC - Roots Medium Connection, from 01 to 02 o'clock, 5 %, within 8 inches of joint: YES43.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active-80% ROOTS85.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped89 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped98 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 5 %, within 8 inches of joint: YESR98 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Active140.6 ft. RMC - Roots Medium Connection, from 01 to 02 o'clock, 5 %, within 8 inches of joint: YES140.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open146.4 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR146.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped153 ft. RFC - Roots Fine Connection, from 10 to 11 o'clock, within 8 inches of joint: YES - 4%153 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active156.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped177.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open188.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open194.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped239.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6", 6" - Open249.2 ft. RMC - Roots Medium Connection, from 01 to 03 o'clock, 5 %, within 8 inches of joint: YES249.2 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS265 ft. AMH - Downstream Manhole, Survey Begins - 3:35AM265 ft. MWM - Water Mark, 50 %of cross sectional area265 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (1)

  • Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR

    118.6 ft. - Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR

Observations (26)

DistanceCodeObservation
176TFCCapped
124.4RMC
0AMH3:35AM
167RMJ
236.8TFCCapped
112RFC4%
70.4TFCCapped
112TFActive
124.4TFOpen
108.3TFCCapped
221.2RMC
167TFActive
15.8RMC
76.2TFOpen
239.9TFCCapped
15.8TFDOpen-90% ROOTS
118.6RMJ
221.2TFDActive-80% ROOTS
179.3TFCCapped
0MWM
118.1TFCCapped
230.3TFOpen
87.2TFOpen
0MWL
25.2TFOpen
265AMH4:05AM

Properties (5)

additional_info
ROOT EVALUATIONONLY
customer
LACSD
datetime
2019-11-08T02:40:47-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false