Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2019, 08:06 PM
  • H 0514_H 0513_1162019_130631.mp4

Date
11/06/2019
W/O
0798185
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00183
PipeID
P20465
Time
12:06 PM
Certificate
U-115-06022628
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8122
Sewer Name
H JOINT OUTFALL H - UNIT 7B
City
INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Capital Improvement Program Assesment
Project
20191106MI_JOINT_OUTFALL_H_UNIT_7B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
H 0514
Downstream MH
H 0513
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
4
Overall Quick
Overall Rating
19
Pipe schematic from manhole H 0514 to H 0513
MH: H 0514MH: H 0513downstream0 ft. MWL - Water Level, 100 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01:02 PM0 ft. MGP - General Photograph - AIRLINE0 ft. MWM - Water Mark, 100 %of cross sectional area2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - MAG COAT, 60%2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. LD - Alignment Down, 45 %2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. MGP - General Photograph - ROACHES > 2002.1 ft. MSA - Survey Abandoned - HIGH WATER

Observation photos (5)

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - MAG COAT, 60%

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - MAG COAT, 60%

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Photograph - ROACHES > 200

    2 ft. - General Photograph - ROACHES > 200

  • Survey Abandoned - HIGH WATER

    2.1 ft. - Survey Abandoned - HIGH WATER

Observations (11)

DistanceCodeObservation
2SZMAG COAT, 60%
0MWL
0AMH01:02 PM
2SSS
2.1MSAHIGH WATER
2SAP
2LD
0MGPAIRLINE
2SRV
2MGPROACHES > 200
0MWM

Properties (6)

additional_info
VIEW OF THE DOWNOLEG PIPE OF THE U/S SIPHON (S/W BARREL)
custom_field_two
3
customer
LACSD
datetime
2019-11-06T12:06:21-08:00
documentation
IGNACIO, FRANKLIN, RUVALCABA, BRAR
is_lateral_inspection
false