Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2019, 09:17 AM
  • 18 0982_18 0981_11122019_013437.mp4

Date
11/12/2019
W/O
0798563
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00717
PipeID
P14833
Time
1:17 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1306R
Sewer Name
18 WORSHAM CREEK RELIEF TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
11
Purpose
Maintenance Related
Project
20191107MDM_WORSHAM_CREEK_RELIEF_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
18 0982
Downstream MH
18 0981
Dir. of Survey
Downstream
Length Surveyed
359.8 ft.
Total Length
359.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 18 0982 to 18 0981
MH: 18 0982MH: 18 0981downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:20AM66.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6" - Active73.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start104.9 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6" - Open130.3 ft. MWLS - Water Level, Sag in pipe, 50 %of cross sectional area, Start135.9 ft. MWLS - Water Level, Sag in pipe, 50 %of cross sectional area, Finish154.7 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6" - Open200.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6" - Open359.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish359.8 ft. AMH - Downstream Manhole, Survey Ends - 1:40AM

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    73.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
104.9TFOpen
200.1TFOpen
0MWM
154.7TFOpen
0MWL
359.2DAGS
130.3MWLS
66.6TFActive
359.8AMH1:40AM
135.9MWLS
73.4DAGS
0AMH1:20AM

Properties (5)

additional_info
ROOT EVALUATION ONLY
customer
LACSD
datetime
2019-11-12T01:17:14-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false