- Date
- 11/06/2019
- W/O
- 0798059
- Weather
- Dry
- Operator/Surveyor
- IGNACIO
- Sewer ID
- Z00307
- PipeID
- P22957
- Time
- 9:48 AM
- Certificate
- U-115-06022628
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G8121
- Sewer Name
- 02 TRACT #5445 TRUNK
- City
- EAST LOS ANGELES
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 12
- Purpose
- Routine Assessment
- Project
- 20191106MI_TRACT_5445_TRUNK
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 18 in.
- Upstream MH
- 02 1436
- Downstream MH
- 02 2421
- Dir. of Survey
- Downstream
- Length Surveyed
- 168.5 ft.
- Total Length
- 168.5 ft.
- Structural Index
- 3
- Structural Quick
- 5131
- Structural Rating
- 10
- O&M Index
- 2
- O&M Quick
- 2100
- O&M Rating
- 2
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 12
Pipe schematic from manhole 02 1436 to 02 2421 Observation photos (4)

2.4 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

2.4 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

87 ft. - General Photograph - AGGREGATE PROJECTING, REBAR VISIBLE

168.5 ft. - Downstream Manhole, Survey Ends - 10:45 AM