Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2019, 11:12 AM
  • 22 0524_22 0523 _09232019_043346.mp4

Date
09/23/2019
W/O
787674
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00791
PipeID
P16864
Time
4:12 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6083
Sewer Name
22 BEN LOMOND TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
26
Purpose
Routine Assessment
Project
WO_787674_TV22006_SEP2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0524
Downstream MH
22 0523
Dir. of Survey
Downstream
Length Surveyed
283.1 ft.
Total Length
283.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 22 0524 to 22 0523
MH: 22 0524MH: 22 0523downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 05240 ft. MGO - General Observation - CONNECTIONS AT BOTH 3 AND 9 O'CLOCK IN MH2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start31.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"35.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"88.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"137 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"185.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"189.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"237.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"280.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish283.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0523283.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observations (18)

DistanceCodeObservation
185.2TFC
280.3SAV
132.3TFC
189.3TFC
2SAV
0MWM
0MWL
283.1AMH22 0523
241.6TF
35.2TFC
137TFC
283.1MGOCONNECTION AT MH 9 O'CLOCK
237.6TFC
31.3TFC
0AMH22 0524
0MGOCONNECTIONS AT BOTH 3 AND 9 O'CLOCK IN MH
88.2TF
84.1TFC

Properties (6)

additional_info
SC378430
custom_field_two
2
customer
LACSD
datetime
2019-09-23T04:12:12-07:00
documentation
PRO PIPE
is_lateral_inspection
false