- Date
- 09/06/2019
- W/O
- 787515
- Weather
- Dry
- Operator/Surveyor
- N.ZAHREDDINE
- Sewer ID
- Z00806
- PipeID
- P16473
- Time
- 2:37 AM
- Certificate
- U-109-7948
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K6080
- Sewer Name
- 22 DISTRICT #22 MAIN RELIEF TRUNK
- City
- COVINA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 31
- Purpose
- Routine Assessment
- Project
- WO_787515_TV22107_SEP2019
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 27 in.
- Width
- 27 in.
- Upstream MH
- 22 1277
- Downstream MH
- H 1512
- Dir. of Survey
- Downstream
- Length Surveyed
- 640.5 ft.
- Total Length
- 640.5 ft.
- Structural Index
- 2
- Structural Quick
- 3225
- Structural Rating
- 16
- O&M Index
- 2
- O&M Quick
- 2Y00
- O&M Rating
- 256
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 272
Pipe schematic from manhole 22 1277 to H 1512 Observation photos (5)

0 ft. - Upstream Manhole, Survey Begins - 22 1277

8.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

34 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

589.1 ft. - Alignment Right, 15 %, Start

615 ft. - Surface Spalling, from 02 to 05 o'clock, within 8 inches of joint: NO, Start