Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2019, 09:58 AM
  • B 0456_B 0455_07262019_030604.mp4

Date
07/26/2019
W/O
766300
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00093
PipeID
P08969
Time
2:58 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
6075
Sewer Name
B JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_766300_TV16079_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
B 0456
Downstream MH
B 0455
Dir. of Survey
Downstream
Length Surveyed
102.8 ft.
Total Length
102.8 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
51
O&M Index
2
O&M Quick
412C
O&M Rating
42
Overall Index
3
Overall Quick
Overall Rating
93
Pipe schematic from manhole B 0456 to B 0455
MH: B 0456MH: B 0455downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 04560 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. MGO - General Observation - MAGNEZIUM H.O COATING ATTATCHED6.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start15.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - POSSIBLE AGGREGATE80.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"102 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish102 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish102.8 ft. AMH - Downstream Manhole, Survey Ends - B 0455

Observation photos (2)

  • General Observation - MAGNEZIUM H.O COATING ATTATCHED

    2 ft. - General Observation - MAGNEZIUM H.O COATING ATTATCHED

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - POSSIBLE AGGREGATE

    15.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - POSSIBLE AGGREGATE

Observations (10)

DistanceCodeObservation
2MGOMAGNEZIUM H.O COATING ATTATCHED
102DAGS
80.7TFC
102.8AMHB 0455
6.1DAGS
0AMHB 0456
0MWL
102SAV
0MWM
15.1SAVPOSSIBLE AGGREGATE

Properties (6)

additional_info
SC377945
custom_field_two
3
customer
LACSD
datetime
2019-07-26T02:58:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false