Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 10, 2019, 07:27 AM
  • 02 1265_02 1264_10092019_234344.mp4

Date
10/10/2019
W/O
792821
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00288
PipeID
P04671
Time
12:27 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7059
Sewer Name
02 MONTEREY PARK DIVERSION TRUNK
City
MONTEREY PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_792821_TV02100_OCT2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1265
Downstream MH
02 1264
Dir. of Survey
Downstream
Length Surveyed
281.4 ft.
Total Length
281.4 ft.
Structural Index
3
Structural Quick
3J2F
Structural Rating
231
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
235
Pipe schematic from manhole 02 1265 to 02 1264
MH: 02 1265MH: 02 1264downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 12650 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area2 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES, Start5.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start106.2 ft. MWL - Water Level, 45 %of cross sectional area279.3 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish281.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish281.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1264

Observation photos (2)

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.4 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2SSS
281.4SAP
5.4SAP
0AMH02 1265
0MWM
0MWL
281.4AMH02 1264
279.3SSS
106.2MWL

Properties (6)

additional_info
SC378659
custom_field_two
2
customer
LACSD
datetime
2019-10-10T00:27:17-07:00
documentation
PROPIPE
is_lateral_inspection
false