Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2019, 07:20 AM
  • 08 0485_08 0484 _08302019_003629.mp4

Date
08/03/2019
W/O
782182
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00019
PipeID
P00543
Time
12:20 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6918
Sewer Name
08 SEPULVEDA-FIGUEROA STREET CONNECTING TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_782182_TV08165_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0484
Downstream MH
08 0485
Dir. of Survey
Upstream
Length Surveyed
224.6 ft.
Total Length
224.6 ft.
Structural Index
3
Structural Quick
443H
Structural Rating
168
O&M Index
2
O&M Quick
2H1B
O&M Rating
103
Overall Index
2
Overall Quick
Overall Rating
271
Pipe schematic from manhole 08 0484 to 08 0485
MH: 08 0484MH: 08 0485upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 04850.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.1 ft. RPLD - Repair Localized Liner Defective, within 8 inches of joint: NO - WRINKLED5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES14.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish21.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start44.3 ft. LL - Alignment Left, 10 %, Finish120.8 ft. LL - Alignment Left, 10 %, Start162.6 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish162.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"190.5 ft. MGO - General Observation - SLIM COAT THROUGHOUT202.5 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start214.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES216.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"219 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start219 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start224.6 ft. MWM - Water Mark, 25 %of cross sectional area224.6 ft. AMH - Downstream Manhole, Survey Begins - 08 0484224.6 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    5.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    9.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start

    22.1 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    203 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    219.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Repair Localized Liner Defective, within 8 inches of joint: NO - WRINKLED

    222.5 ft. - Repair Localized Liner Defective, within 8 inches of joint: NO - WRINKLED

Observations (20)

DistanceCodeObservation
0MWM
203CL
222.5RPLDWRINKLED
34.1MGOSLIM COAT THROUGHOUT
210CL
223.8CM
5.6DAGS
0AMH08 0484
224.6AMH08 0485
8.5TFC
180.3LL
219.6FM
9.7FM
223.8DAGS
103.8LL
5.6CM
22.1CL
0MWL
62CL
62TFC

Properties (6)

additional_info
SC378515
custom_field_two
2
customer
LACSD
datetime
2019-08-03T00:20:19-07:00
documentation
PROPIPE
is_lateral_inspection
false