Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 26, 2019, 05:35 AM
  • F 0302_F 0145 _09252019_224930.mp4

Date
09/25/2019
W/O
787525
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00690
PipeID
P14201
Time
10:35 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6947
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
34
Purpose
Routine Assessment
Project
RFIR_WO_787525_TV18167_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
F 0302
Downstream MH
F 0145
Dir. of Survey
Downstream
Length Surveyed
31.4 ft.
Total Length
31.4 ft.
Structural Index
4
Structural Quick
4331
Structural Rating
15
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole F 0302 to F 0145
MH: F 0302MH: F 0145downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 03020 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT 9'05.1 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Change5.5 ft. FM - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES8.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES30.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish31.3 ft. MGO - General Observation - CONNECTION AT 3 O'CLOCK31.4 ft. AMH - Downstream Manhole, Survey Ends - F 0145

Observation photos (3)

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Change

    5.1 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Change

  • Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

    5.5 ft. - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    8.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
30.8FM
31.3MGOCONNECTION AT 3 O'CLOCK
0MWM
0AMHF 0302
5.5FM
0MWL
5.1FM
8.1CM
31.4AMHF 0145
0MGOCONNECTION AT 9'0

Properties (6)

additional_info
SC378546
custom_field_two
2
customer
LACSD
datetime
2019-09-25T22:35:06-07:00
documentation
PROPIPE
is_lateral_inspection
false