Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 11, 2019, 06:18 AM
  • 14 1124A_14 1124_10102019_233330.mp4

Date
10/10/2019
W/O
787589
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01179
PipeID
P26077
Time
11:18 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7032
Sewer Name
14 WEST SIDE RELIEF TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_787589_TV14056_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 1124A
Downstream MH
14 1124
Dir. of Survey
Downstream
Length Surveyed
448.4 ft.
Total Length
448.4 ft.
Structural Index
2
Structural Quick
2Q00
Structural Rating
178
O&M Index
2
O&M Quick
2Q00
O&M Rating
178
Overall Index
2
Overall Quick
Overall Rating
356
Pipe schematic from manhole 14 1124A to 14 1124
MH: 14 1124AMH: 14 1124downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 1124A2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start446.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish447 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish448.4 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE448.4 ft. AMH - Downstream Manhole, Survey Ends - 14 1124

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
2SSS
0MWL
448.4MGOCONN @ MH 9 O'CLOCK/ACTIVE
447SSS
448.4AMH14 1124
2DAGS
0MWM
0AMH14 1124A
446.2DAGS

Properties (7)

additional_info
SC378701
custom_field_two
4
customer
LACSD
datetime
2019-10-10T23:18:43-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
40175