Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 21, 2019, 07:45 AM
  • 29 0455_29 0454 _10072019_122036.mp4

Date
08/21/2019
W/O
782252
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00537
PipeID
P24496
Time
12:45 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6908
Sewer Name
29 21ST STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_782252_TV29055_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0455
Downstream MH
29 0454
Dir. of Survey
Downstream
Length Surveyed
320.2 ft.
Total Length
320.2 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
117
O&M Index
2
O&M Quick
2H00
O&M Rating
90
Overall Index
2
Overall Quick
Overall Rating
207
Pipe schematic from manhole 29 0455 to 29 0454
MH: 29 0455MH: 29 0454downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 04550 ft. MWL - Water Level, 5 %of cross sectional area13.8 ft. CS - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES35.1 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES51.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"53.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"67.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES92.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start151.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"152.7 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: NO158.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start241.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES242.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"247.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"313.6 ft. FS - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES319.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish319.5 ft. B - Broken, from 12 to 08 o'clock, within 8 inches of joint: YES319.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish320.2 ft. AOC - Drop Connection, Survey Ends - 29 0454

Observation photos (9)

  • Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

    13.8 ft. - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    35.1 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    67.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    92.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: NO

    152.7 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: NO

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    158.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    241.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    313.6 ft. - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Broken, from 12 to 08 o'clock, within 8 inches of joint: YES

    319.5 ft. - Broken, from 12 to 08 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
247.7TF
0MWM
35.1CM
319.5DAGS
92.8DAGS
313.6FS
151.2TF
158.9CM
152.7CL
67.8CL
0AMH29 0455
320.2AOC29 0454
319.5B
0MWL
242.2TFC
53.8TFC
51.3TFC
319.5CM
241.2FM
13.8CS

Properties (6)

additional_info
SC378505
custom_field_two
2
customer
LACSD
datetime
2019-08-21T00:45:45-07:00
documentation
PROPIPE
is_lateral_inspection
false