Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 20, 2019, 08:07 AM
  • 01 0135_01 0134_09202019_012345.mp4

Date
09/20/2019
W/O
787653
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00204
PipeID
P02079
Time
1:07 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6939
Sewer Name
01 COMPTON CREEK EXTENSION TRUNK, SECTION 2
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_787653_TV01272_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0135
Downstream MH
01 0134
Dir. of Survey
Downstream
Length Surveyed
153.7 ft.
Total Length
153.7 ft.
Structural Index
4
Structural Quick
4E00
Structural Rating
116
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
120
Pipe schematic from manhole 01 0135 to 01 0134
MH: 01 0135MH: 01 0134downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 01350 ft. MWL - Water Level, 35 %of cross sectional area0.1 ft. MWM - Water Mark, 55 %of cross sectional area5.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start152.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish153.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0134

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
152.3FM
0AMH01 0135
5.6FM
0.1MWM
153.7AMH01 0134
0MWL

Properties (6)

additional_info
SC378538
custom_field_two
2
customer
LACSD
datetime
2019-09-20T01:07:03-07:00
documentation
PROPIPE
is_lateral_inspection
false