Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 16, 2019, 04:46 AM
  • 02 0861_02 0860_10152019_214947.mp4

Date
10/15/2019
W/O
787659
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00297
PipeID
P03428
Time
9:46 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7038
Sewer Name
02 OLD RIVER SCHOOL ROAD RELIEF TRUNK, SECTS 2&3
City
DOWNEY
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_787659_TV02299_SEP2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
02 0860
Downstream MH
02 0861
Dir. of Survey
Upstream
Length Surveyed
635.4 ft.
Total Length
635.4 ft.
Structural Index
3
Structural Quick
5X3X
Structural Rating
1260
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
1260
Pipe schematic from manhole 02 0860 to 02 0861
MH: 02 0860MH: 02 0861upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 08611.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish3.4 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 80% MAG3.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish633.4 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 80% MAG633.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start633.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start633.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start635.4 ft. AMH - Downstream Manhole, Survey Begins - 02 0860635.4 ft. MWM - Water Mark, 30 %of cross sectional area635.4 ft. MWL - Water Level, 25 %of cross sectional area

Observation photos (2)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
632SZ80% MAG
2SZ80% MAG
632SRV
0AMH02 0860
2SSS
0MWM
635.4AMH02 0861
0MWL
633.6SAP
633.6SSS
2SAP
2SRV

Properties (6)

additional_info
SC378707
custom_field_two
2
customer
LACSD
datetime
2019-10-15T21:46:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false