Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 1, 2019, 04:31 PM
  • B 0491_H 1341 _10012019_110714.mp4

Date
10/01/2019
W/O
788122
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00085
PipeID
P26176
Time
9:31 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6963
Sewer Name
B JOINT OUTFALL B - UNIT 2B
City
EL MONTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
32
Purpose
Routine Assessment
Project
RFIR_WO_788122_TV15203_SEP2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
B 0491
Downstream MH
H 1341
Dir. of Survey
Downstream
Length Surveyed
829 ft.
Total Length
829 ft.
Structural Index
3
Structural Quick
513`
Structural Rating
829
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
834
Pipe schematic from manhole B 0491 to H 1341
MH: B 0491MH: H 1341downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 04910 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.9 ft. VC - Vermin Cockroach2.9 ft. MGO - General Observation - MAG COAT THROUGHOUT14.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start353.1 ft. SRP - Surface Reinforcement Projecting, from 07 to 11 o'clock, within 8 inches of joint: NO728 ft. SRV - Surface Reinforcement Visible, from 07 to 01 o'clock, within 8 inches of joint: YES, Change828 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish829 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish829 ft. MSA - Survey Abandoned - FLIPPED OVER UNABLE TO COMPLETE829 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Vermin Cockroach

    2.9 ft. - Vermin Cockroach

  • General Observation - MAG COAT THROUGHOUT

    2.9 ft. - General Observation - MAG COAT THROUGHOUT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    14.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Projecting, from 07 to 11 o'clock, within 8 inches of joint: NO

    353.1 ft. - Surface Reinforcement Projecting, from 07 to 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 07 to 01 o'clock, within 8 inches of joint: YES, Change

    728 ft. - Surface Reinforcement Visible, from 07 to 01 o'clock, within 8 inches of joint: YES, Change

Observations (14)

DistanceCodeObservation
2.9SAV
829SAV
353.1SRP
0AMHB 0491
829MSAFLIPPED OVER UNABLE TO COMPLETE
828DAGS
0MWM
0MWL
2.9VC
829SSS
2.1DAGS
14.9SSS
728SRV
2.9MGOMAG COAT THROUGHOUT

Properties (6)

additional_info
SC378575
custom_field_two
5
customer
LACSD
datetime
2019-10-01T09:31:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false