- Date
- 10/01/2019
- W/O
- 788122
- Weather
- Dry
- Operator/Surveyor
- J. VARGAS
- Sewer ID
- Z00085
- PipeID
- P08801
- Time
- 11:18 AM
- Certificate
- U-209-8149
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K6963
- Sewer Name
- B JOINT OUTFALL B - UNIT 2B
- City
- EL MONTE
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 32
- Purpose
- Routine Assessment
- Project
- RFIR_WO_788122_TV15203_SEP2019
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 57 in.
- Width
- 57 in.
- Upstream MH
- H 1341
- Downstream MH
- B 0219
- Dir. of Survey
- Downstream
- Length Surveyed
- 206.1 ft.
- Total Length
- 206.1 ft.
- Structural Index
- 2
- Structural Quick
- 3G2G
- Structural Rating
- 202
- O&M Index
- 2
- O&M Quick
- 2B00
- O&M Rating
- 32
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 234
Pipe schematic from manhole H 1341 to B 0219 Observation photos (4)

1.1 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - General Observation - MAG COAT THROUGHOUT

127.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start