Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 11, 2019, 08:27 AM
  • 14 0121_14 0120 _09112019_014652.mp4

Date
09/11/2019
W/O
787631
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00571
PipeID
P18151
Time
1:27 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6892
Sewer Name
14 DISTRICT #14 OUTFALL TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_787631_TV14075_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0121
Downstream MH
14 0120
Dir. of Survey
Downstream
Length Surveyed
292.5 ft.
Total Length
292.5 ft.
Structural Index
4
Structural Quick
4G3C
Structural Rating
206
O&M Index
2
O&M Quick
2S00
O&M Rating
196
Overall Index
3
Overall Quick
Overall Rating
402
Pipe schematic from manhole 14 0121 to 14 0120
MH: 14 0121MH: 14 0120downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 14 01210 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.2 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"12.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start59.2 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"74.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start74.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish92.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start116.6 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"128.3 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"175.2 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"203.6 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"228.6 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"263 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish263 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start269.3 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"291 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish291 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish292 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish292.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0120

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    74.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    263 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
12.6CM
74.2FM
292.5AMH14 0120
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
292DAE
0AMH14 0121
128.3TBA
0MWM
0MWL
269.3TBA
59.2TBA
263FM
2DAGS
92.1DAE
203.6TBA
291CM
175.2TBA
6.2TBA
291DAGS
116.6TBA
228.6TBA
74.2CM
263CM

Properties (6)

additional_info
SC378608
custom_field_two
2
customer
LACSD
datetime
2019-09-11T01:27:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false