Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 9, 2019, 11:36 AM
  • 05 2405_05 2404 _09092019_220911.mp4

Date
09/09/2019
W/O
787626
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00481
PipeID
P07516
Time
4:36 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6926
Sewer Name
05 MANCHESTER AVENUE PUMP TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
11
Purpose
Routine Assessment
Project
WO_787626_TV05304_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
05 2405
Downstream MH
05 2404
Dir. of Survey
Downstream
Length Surveyed
239.3 ft.
Total Length
239.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2H00
O&M Rating
92
Overall Index
2
Overall Quick
Overall Rating
92
Pipe schematic from manhole 05 2405 to 05 2404
MH: 05 2405MH: 05 2404downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 24055.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start140.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 8"236.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish239.3 ft. AMH - Downstream Manhole, Survey Ends - 05 2404

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    5.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
236.6DAGS
5.8DAGS
140.7TFA
0MWM
239.3AMH05 2404
0MWL
0AMH05 2405

Properties (6)

additional_info
SC378524
custom_field_two
4
customer
LACSD
datetime
2019-09-09T04:36:35-07:00
documentation
PROPIPE
is_lateral_inspection
false