Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 30, 2019, 03:38 PM
  • H 0479_H 0478_09302019_111236.mp4

Date
09/30/2019
W/O
787580
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00178
PipeID
P10853
Time
8:38 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6961
Sewer Name
H JOINT OUTFALL H - UNIT 5B
City
LA PUENTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_787580_TV15064_SEP2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
H 0479
Downstream MH
H 0478
Dir. of Survey
Downstream
Length Surveyed
672.8 ft.
Total Length
672.8 ft.
Structural Index
3
Structural Quick
3Z2Y
Structural Rating
663
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
668
Pipe schematic from manhole H 0479 to H 0478
MH: H 0479MH: H 0478downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTIONS AT BOTH 9 AND 10 O'CLOCK IN MH0 ft. AMH - Upstream Manhole, Survey Begins - H 04790 ft. MWL - Water Level, 30 %of cross sectional area5.5 ft. VC - Vermin Cockroach5.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.6 ft. MGO - General Observation - MAG COAT THROUGHOUT14.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"53.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start266.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"291.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"328.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"421.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"478.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"540.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"615.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"672 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish672.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"672.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish672.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish672.8 ft. AMH - Downstream Manhole, Survey Ends - H 0478

Observation photos (5)

  • Vermin Cockroach

    5.5 ft. - Vermin Cockroach

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT THROUGHOUT

    5.6 ft. - General Observation - MAG COAT THROUGHOUT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    14.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    53.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
5.6MGOMAG COAT THROUGHOUT
540.5TFA
0MWM
0MGOCONNECTIONS AT BOTH 9 AND 10 O'CLOCK IN MH
35.8TFA
14.3SSS
328.3TF
0AMHH 0479
478.4TFA
672.8SAP
421.2TF
291.1TFC
672.8SSS
0MWL
5.5VC
266.6TFC
53.1DAGS
672.8AMHH 0478
672DAGS
615.2TF
672.4TFA
5.5SAP

Properties (6)

additional_info
SC378573
custom_field_two
3
customer
LACSD
datetime
2019-09-30T08:38:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false