Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 30, 2019, 08:05 PM
  • H 0476_H 0475_09302019_132508.mp4

Date
09/30/2019
W/O
787580
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00178
PipeID
P10852
Time
1:05 PM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6961
Sewer Name
H JOINT OUTFALL H - UNIT 5B
City
LA PUENTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_787580_TV15064_SEP2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
H 0476
Downstream MH
H 0475
Dir. of Survey
Downstream
Length Surveyed
379.1 ft.
Total Length
379.1 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
375
O&M Index
1
O&M Quick
1600
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
381
Pipe schematic from manhole H 0476 to H 0475
MH: H 0476MH: H 0475downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 04760 ft. VC - Vermin Cockroach, within 8 inches of joint: YES0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2.2 ft. MGO - General Observation - MAG COAT THROUGHOUT2.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"24.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"81.8 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"141.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"141.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"238.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"265.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"331.1 ft. LR - Alignment Right, 10 %, Start355 ft. LR - Alignment Right, 10 %, Finish379 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish379.1 ft. AMH - Downstream Manhole, Survey Ends - H 0475379.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Vermin Cockroach, within 8 inches of joint: YES

    0 ft. - Vermin Cockroach, within 8 inches of joint: YES

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT THROUGHOUT

    2.2 ft. - General Observation - MAG COAT THROUGHOUT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Alignment Right, 10 %, Start

    331.1 ft. - Alignment Right, 10 %, Start

Observations (21)

DistanceCodeObservation
0AMHH 0476
2.2MGOMAG COAT THROUGHOUT
0VC
379SSS
81.8TFA
2.2SAP
265.7TF
2SSS
24.3TFA
379.1AMHH 0475
0MWM
141.9TFC
331.1LR
0MGOCONNECTION AT MH 3 O'CLOCK
9TFA
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK
355LR
379.1SAP
238.9TFC
141.7TFA

Properties (6)

additional_info
SC378573
custom_field_two
3
customer
LACSD
datetime
2019-09-30T13:05:03-07:00
documentation
PRO PIPE
is_lateral_inspection
false