- Date
- 09/03/2019
- W/O
- 787493
- Weather
- Dry
- Operator/Surveyor
- N.ZAHREDDINE
- Sewer ID
- Z00646
- PipeID
- P13237
- Time
- 1:41 AM
- Certificate
- U-109-7948
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K6077
- Sewer Name
- 16 ARROYO SECO TRUNK, SECTION 3
- City
- SOUTH PASADENA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 16
- Page No.
- 17
- Purpose
- Routine Assessment
- Project
- RFIR_WO_787493_TV16114_SEP2019
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- 16 0194
- Downstream MH
- 16 0193
- Dir. of Survey
- Downstream
- Length Surveyed
- 91.2 ft.
- Total Length
- 91.2 ft.
- Structural Index
- 3
- Structural Quick
- 514C
- Structural Rating
- 105
- O&M Index
- 2
- O&M Quick
- 412B
- O&M Rating
- 39
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 144
Pipe schematic from manhole 16 0194 to 16 0193 Observation photos (6)

0.1 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

17 ft. - Surface Reinforcement Visible, from 08 to 11 o'clock, within 8 inches of joint: NO

21 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

22.1 ft. - General Observation - MAGNEZIUM H.O COATING START

25.1 ft. - Alignment Left, 5 %