Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 27, 2018, 10:30 AM
  • 02 0133_02 0132 _11272018_023637.mp4

Date
11/27/2018
W/O
735123
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02435
Time
2:30 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6230
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_735123_TV02373_NOV2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
02 0133
Downstream MH
02 0132
Dir. of Survey
Downstream
Length Surveyed
63.8 ft.
Total Length
63.8 ft.
Structural Index
3
Structural Quick
3A00
Structural Rating
36
O&M Index
3
O&M Quick
3A00
O&M Rating
36
Overall Index
3
Overall Quick
Overall Rating
72
Pipe schematic from manhole 02 0133 to 02 0132
MH: 02 0133MH: 02 0132downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 01330 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start - SLUDGE2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start63.8 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Finish63.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK63.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish63.8 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK63.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0132

Observation photos (2)

  • Deposits Settled Other,  15 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: NO, Start - SLUDGE

    2.1 ft. - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start - SLUDGE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MWL
0AMH02 0133
63.8DSZ
0MWM
63.8MGOCONNECTION AT MH 9 O'CLOCK
63.8SAP
2.1DSZSLUDGE
63.8MGOCONNECTION AT MH 12 O'CLOCK
63.8AMH02 0132
2.1SAP

Properties (6)

additional_info
SC365458
custom_field_two
2
customer
LACSD
datetime
2018-11-27T02:30:16-08:00
documentation
PROPIPE
is_lateral_inspection
false