Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 3, 2019, 09:31 AM
  • 08 0327_08 0326_09032019_025001.mp4

Date
09/03/2019
W/O
787537
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00013
PipeID
P00375
Time
2:31 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6921
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_787537_TV08155_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0326
Downstream MH
08 0327
Dir. of Survey
Upstream
Length Surveyed
339.4 ft.
Total Length
339.4 ft.
Structural Index
3
Structural Quick
4L3L
Structural Rating
599
O&M Index
2
O&M Quick
2L11
O&M Rating
133
Overall Index
3
Overall Quick
Overall Rating
732
Pipe schematic from manhole 08 0326 to 08 0327
MH: 08 0326MH: 08 0327upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 03272.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish2.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish3.4 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - @ MH3.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish3.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish36.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN91.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"145.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"196.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"245.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"290.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"329.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"334.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start334.4 ft. DAGS - Deposits Attached Grease, 0 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start337.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start337.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start339.4 ft. AMH - Downstream Manhole, Survey Begins - 08 0326339.4 ft. MWL - Water Level, 10 %of cross sectional area339.4 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 0 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    5 ft. - Deposits Attached Grease, 0 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
336VC@ MH
248.3TFC
337.1DAGS
336CM
336SSS
9.6TFC
0AMH08 0326
0MWL
193.6TFC
5FM
94.2TFC
142.5TFC
303.3TFOPEN
0MWM
337.1FM
5DAGS
2CM
49.2TFC
2SSS
339.4AMH08 0327

Properties (6)

additional_info
SC378518
custom_field_two
2
customer
LACSD
datetime
2019-09-03T02:31:46-07:00
documentation
PROPIPE
is_lateral_inspection
false