Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 3, 2019, 10:59 AM
  • 08 0323_08 0322_09032019_041416.mp4

Date
09/03/2019
W/O
787537
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00013
PipeID
P00371
Time
3:59 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6921
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_787537_TV08155_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0323
Downstream MH
08 0322
Dir. of Survey
Downstream
Length Surveyed
253.4 ft.
Total Length
253.4 ft.
Structural Index
3
Structural Quick
4I3I
Structural Rating
446
O&M Index
2
O&M Quick
2I12
O&M Rating
100
Overall Index
3
Overall Quick
Overall Rating
546
Pipe schematic from manhole 08 0323 to 08 0322
MH: 08 0323MH: 08 0322downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONN 9 O'CLOCK @ MH/ACTIVE0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 03230 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - @ MH2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"54.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"105.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN159.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN206.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"250 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish250 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish251 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - @ MH251.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish251.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish253.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0322253.4 ft. MGO - General Observation - CONN 9 O'CLOCK @ MH/ACTIVE253.4 ft. MGO - General Observation - CONN 3 O'CLOCK @ MH/ACTIVE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
253.4AMH08 0322
0MWM
0MGOCONN 9 O'CLOCK @ MH/ACTIVE
105.5TFOPEN
253.4MGOCONN 9 O'CLOCK @ MH/ACTIVE
251.2FM
5.3FM
206.8TFC
5DAGS
2SSS
0MWL
159.2TFOPEN
250SSS
251VC@ MH
54.1TFC
251.2DAGS
253.4MGOCONN 3 O'CLOCK @ MH/ACTIVE
0AMH08 0323
11.4TFC
0VC@ MH
250CM
2CM

Properties (6)

additional_info
SC378518
custom_field_two
2
customer
LACSD
datetime
2019-09-03T03:59:46-07:00
documentation
PROPIPE
is_lateral_inspection
false