Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 11, 2019, 06:59 AM
  • 14 0124_14 0123A_09112019_000550.mp4

Date
09/10/2019
W/O
787496
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00571
PipeID
P26493
Time
11:59 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6891
Sewer Name
14 DISTRICT #14 OUTFALL TRUNK
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_787496_TV14066_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0123A
Downstream MH
14 0124
Dir. of Survey
Upstream
Length Surveyed
70.4 ft.
Total Length
70.4 ft.
Structural Index
3
Structural Quick
3921
Structural Rating
29
O&M Index
2
O&M Quick
2B00
O&M Rating
26
Overall Index
2
Overall Quick
Overall Rating
55
Pipe schematic from manhole 14 0123A to 14 0124
MH: 14 0123AMH: 14 0124upstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 0124, ABANDONED MH.2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish7.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish54.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start62.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES68.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start70.4 ft. AMH - Downstream Manhole, Survey Begins - 14 0123A70.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK70.4 ft. MWL - Water Level, 20 %of cross sectional area70.4 ft. MWM - Water Mark, 40 %of cross sectional area

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    7.5 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    16.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Upstream Manhole, Survey Ends - 14 0124, ABANDONED MH.

    70.4 ft. - Upstream Manhole, Survey Ends - 14 0124, ABANDONED MH.

Observations (10)

DistanceCodeObservation
7.5CL
63.3CM
0AMH14 0123A
0MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK
0MWL
16.3CM
2DAGS
70.4AMH14 0124, ABANDONED MH.
0MWM
67.8DAGS

Properties (6)

additional_info
SC378607
custom_field_two
3
customer
LACSD
datetime
2019-09-10T23:59:50-07:00
documentation
PRO PIPE
is_lateral_inspection
false