Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 7, 2019, 06:31 AM
  • 22 0972_22 0971_08062019_235301.mp4

Date
08/06/2019
W/O
782130
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00790
PipeID
P17342
Time
11:31 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5954
Sewer Name
22 BASE LINE TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_782130_TV22002_AUG2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0972
Downstream MH
22 0971
Dir. of Survey
Downstream
Length Surveyed
304.4 ft.
Total Length
304.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 22 0972 to 22 0971
MH: 22 0972MH: 22 0971downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 09720 ft. MWM - Water Mark, 30 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.8 ft. MGO - General Observation - MAG COAT THROUGHOUT63.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"141.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"165.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"222.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"226.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"301.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish304.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0971304.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (10)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT THROUGHOUT

    4.8 ft. - General Observation - MAG COAT THROUGHOUT

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    63.9 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    116.6 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    141.3 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    165.7 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    222.4 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    226.6 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    267.3 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • General Observation - CONNECTION AT MH 9 O'CLOCK

    304.4 ft. - General Observation - CONNECTION AT MH 9 O'CLOCK

Observations (15)

DistanceCodeObservation
267.3TF
301.7SAV
141.3TFC
165.7TF
63.9TFC
2.1SAV
222.4TF
304.4AMH22 0971
116.6TF
0MWL
0AMH22 0972
0MWM
226.6TF
4.8MGOMAG COAT THROUGHOUT
304.4MGOCONNECTION AT MH 9 O'CLOCK

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-06T23:31:57-07:00
documentation
PRO PIPE
is_lateral_inspection
false