Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 8, 2019, 08:20 AM
  • 22 0964_22 0963_08082019_014229.mp4

Date
08/08/2019
W/O
782130
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00790
PipeID
P17334
Time
1:20 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5955
Sewer Name
22 BASE LINE TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_782130_TV22002_AUG2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0963
Downstream MH
22 0964
Dir. of Survey
Upstream
Length Surveyed
365 ft.
Total Length
365 ft.
Structural Index
2
Structural Quick
3M2M
Structural Rating
423
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
424
Pipe schematic from manhole 22 0963 to 22 0964
MH: 22 0963MH: 22 0964upstream0 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish8.3 ft. AMH - Upstream Manhole, Survey Ends - 22 09648.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK9 ft. SRI - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish11.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish96.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"104 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"148.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"253.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"262.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"295.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"305.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"308.5 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"355 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start355.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"358 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - COCKROACHES IN LINE363 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start363 ft. SRI - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Start363 ft. MGO - General Observation - MAG COAT THROUGHOUT365 ft. MWL - Water Level, 15 %of cross sectional area365 ft. AMH - Downstream Manhole, Survey Begins - 22 0963365 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (18)

  • Downstream Manhole, Survey Begins - 22 0963

    0 ft. - Downstream Manhole, Survey Begins - 22 0963

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT THROUGHOUT

    2 ft. - General Observation - MAG COAT THROUGHOUT

  • Vermin Cockroach, within 8 inches of joint: YES - COCKROACHES IN LINE

    7 ft. - Vermin Cockroach, within 8 inches of joint: YES - COCKROACHES IN LINE

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    9.3 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    56.5 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    59.6 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    69.9 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    102.9 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    111.8 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    159.3 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    191.6 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    216.1 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    261 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    268.3 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • General Observation - CONNECTION AT MH 3 O'CLOCK

    356.6 ft. - General Observation - CONNECTION AT MH 3 O'CLOCK

Observations (24)

DistanceCodeObservation
216.1TFC
7VCCOCKROACHES IN LINE
356.7AMH22 0964
2SAV
365SSS
2SRI
0MWL
356SRI
2MGOMAG COAT THROUGHOUT
9.3TF
10SSS
356.6MGOCONNECTION AT MH 3 O'CLOCK
191.6TF
0AMH22 0963
268.3TF
69.9TFC
0MWM
56.5TB
159.3TFC
261TFC
59.6TFC
102.9TFC
111.8TFC
353.6SAV

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-08T01:20:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false