Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 8, 2019, 10:19 AM
  • H 0719A_H 0719_08082019_033720.mp4

Date
08/08/2019
W/O
776981
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00941
PipeID
P21387
Time
3:19 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6855
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_776981_TV22077_JUL2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0719A
Downstream MH
H 0719
Dir. of Survey
Downstream
Length Surveyed
521.7 ft.
Total Length
521.7 ft.
Structural Index
3
Structural Quick
3T00
Structural Rating
312
O&M Index
2
O&M Quick
412T
O&M Rating
212
Overall Index
3
Overall Quick
Overall Rating
524
Pipe schematic from manhole H 0719A to H 0719
MH: H 0719AMH: H 0719downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 0719A - "MH CLOSED-UP"0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. MGO - General Observation - MAG COATING THROUGHOUT 60%.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start521.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish521.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish521.7 ft. AMH - Downstream Manhole, Survey Ends - H 0719, RUN LIST STATES MH AT 695'.

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2MGOMAG COATING THROUGHOUT 60%.
2SAP
0AMHH 0719A - "MH CLOSED-UP"
0MWM
2DAGS
0MWL
521.2SAP
521.2DAGS
521.7AMHH 0719, RUN LIST STATES MH AT 695'.

Properties (6)

additional_info
SC378324
custom_field_two
2
customer
LACSD
datetime
2019-08-08T03:19:24-07:00
documentation
PRO PIPE
is_lateral_inspection
false