Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2019, 09:29 AM
  • H 0718_15 0001_13092019_030420.mp4

Date
09/13/2019
W/O
776981
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00941
PipeID
P11127
Time
2:29 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6931
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
BASSETT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_776981_TV22077_JUL2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
15 0001
Downstream MH
H 0718
Dir. of Survey
Upstream
Length Surveyed
606 ft.
Total Length
606 ft.
Structural Index
3
Structural Quick
3W00
Structural Rating
357
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
357
Pipe schematic from manhole 15 0001 to H 0718
MH: 15 0001MH: H 0718upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 07180.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish598.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start598.2 ft. MGO - General Observation - 70% MAG COATING THROUGHOUT PIPE606 ft. MWM - Water Mark, 40 %of cross sectional area606 ft. MGO - General Observation - CONNECTION AT 3 O'CLOCK606 ft. AMH - Downstream Manhole, Survey Begins - 15 0001606 ft. MWL - Water Level, 40 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.8 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
7.8SAV
605.2SAV
7.8MGO70% MAG COATING THROUGHOUT PIPE
0MWM
0MGOCONNECTION AT 3 O'CLOCK
0AMH15 0001
0MWL
606AMHH 0718

Properties (6)

additional_info
SC378530
custom_field_two
3
customer
LACSD
datetime
2019-09-13T02:29:47-07:00
documentation
PROPIPE
is_lateral_inspection
false