Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2019, 05:10 AM
  • H 0715_H 0714_12082019_230147.mp4

Date
08/12/2019
W/O
776981
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00941
PipeID
P11123
Time
10:10 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6858
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
LA PUENTE
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_776981_TV22077_JUL2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0715
Downstream MH
H 0714
Dir. of Survey
Downstream
Length Surveyed
1004.4 ft.
Total Length
1004.4 ft.
Structural Index
3
Structural Quick
3g2g
Structural Rating
1000
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
1008
Pipe schematic from manhole H 0715 to H 0714
MH: H 0715MH: H 0714downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 07152 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start7.5 ft. MGO - General Observation - MAG COATING THROUGHOUT 75%764 ft. MGO - General Observation - SMALL TEAR IN LINER @ 12 O'CLOCK765.2 ft. MMC - Material Change, Polyvinyl Chloride (PVC)778.1 ft. MMC - Material Change, Concrete pipe (non-reinfored)1004.4 ft. MGO - General Observation - RUN LIST STATES D/S MH TO BE H 0475, NO CONNECTION AT MH H 0475. ACTUAL D/S MH IS H 0714. SECTION INFO CHANGED TO REFLECT ACTUAL D/S MH.1004.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1004.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish1004.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1004.4 ft. AMH - Downstream Manhole, Survey Ends - H 0714

Observation photos (6)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Material Change, Polyvinyl Chloride (PVC)

    765.2 ft. - Material Change, Polyvinyl Chloride (PVC)

  • Material Change, Concrete pipe (non-reinfored)

    778.1 ft. - Material Change, Concrete pipe (non-reinfored)

  • General Observation - RUN LIST STATES D/S MH TO BE H 0475, NO CONNECTION AT MH H 0475. ACTUAL D/S MH IS H 0714. SECTION INFO CHANGED TO REFLECT ACTUAL D/S MH.

    1004.4 ft. - General Observation - RUN LIST STATES D/S MH TO BE H 0475, NO CONNECTION AT MH H 0475. ACTUAL D/S MH IS H 0714. SECTION INFO CHANGED TO REFLECT ACTUAL D/S MH.

Observations (15)

DistanceCodeObservation
2SSS
2SAP
765.2MMC
7.5MGOMAG COATING THROUGHOUT 75%
1004.4MGORUN LIST STATES D/S MH TO BE H 0475, NO CONNECTION AT MH H 0475. ACTUAL D/S MH IS H 0714. SECTION INFO CHANGED TO REFLECT ACTUAL D/S MH.
1004.4SSS
1004.4DAGS
1004.4SAP
778.1MMC
0MWM
1004.4AMHH 0714
0MWL
2DAGS
764MGOSMALL TEAR IN LINER @ 12 O'CLOCK
0AMHH 0715

Properties (6)

additional_info
SC378327
custom_field_two
2
customer
LACSD
datetime
2019-08-12T22:10:43-07:00
documentation
PRO PIPE
is_lateral_inspection
false