Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2019, 09:57 AM
  • 19 0076_19 0075 _08202019_032021.mp4

Date
08/20/2019
W/O
782228
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00724
PipeID
P15108
Time
2:57 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6907
Sewer Name
19 ELAINE AVENUE TRUNK
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_782228_TV19057_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
19 0076
Downstream MH
19 0075
Dir. of Survey
Downstream
Length Surveyed
349 ft.
Total Length
349 ft.
Structural Index
3
Structural Quick
4231
Structural Rating
14
O&M Index
2
O&M Quick
4331
O&M Rating
264
Overall Index
2
Overall Quick
Overall Rating
278
Pipe schematic from manhole 19 0076 to 19 0075
MH: 19 0076MH: 19 0075downstream0 ft. MWL - Water Level, 60 %of cross sectional area0 ft. MCU - Camera Underwater, Start0 ft. AMH - Upstream Manhole, Survey Begins - 19 007613.4 ft. MCU - Camera Underwater, Finish13.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start13.5 ft. MWL - Water Level, 40 %of cross sectional area28.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES52.3 ft. JSM - Joint Separated Medium64.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start68.4 ft. FS - Fracture Spiral, from 11 to 02 o'clock, within 8 inches of joint: YES83.3 ft. MGO - General Observation - LIGHT STEAM IN SEWER93.4 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES170.6 ft. FM - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES186.6 ft. CS - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES344.6 ft. FM - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES347.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish347.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish349 ft. AMH - Downstream Manhole, Survey Ends - 19 0075

Observation photos (9)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    13.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    28.6 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Joint Separated Medium

    52.3 ft. - Joint Separated Medium

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    64.8 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Spiral, from 11 to 02 o'clock, within 8 inches of joint: YES

    68.4 ft. - Fracture Spiral, from 11 to 02 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    93.4 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    170.6 ft. - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

    186.6 ft. - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    344.6 ft. - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
186.6CS
13.5DAGS
0MWL
344.6FM
0MCU
83.3MGOLIGHT STEAM IN SEWER
64.8DAE
28.6RFJ
347.5DAE
170.6FM
68.4FS
13.5MWL
349AMH19 0075
13.4MCU
347.5DAGS
0AMH19 0076
93.4ID
52.3JSM

Properties (6)

additional_info
SC378504
custom_field_two
2
customer
LACSD
datetime
2019-08-20T02:57:29-07:00
documentation
PROPIPE
is_lateral_inspection
false