- Date
- 08/05/2019
- W/O
- 776985
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00111
- PipeID
- P09203
- Time
- 1:53 AM
- Certificate
- U-715-07000770
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K6732
- Sewer Name
- B JOINT OUTFALL B - UNIT 8H
- City
- DUARTE
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 01
- Purpose
- Routine Assessment
- Project
- RFIR_WO_776985_TV22165_JUL2019
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 10 in.
- Width
- 10 in.
- Upstream MH
- B 0736
- Downstream MH
- B 0735
- Dir. of Survey
- Downstream
- Length Surveyed
- 233.8 ft.
- Total Length
- 233.8 ft.
- Structural Index
- 4
- Structural Quick
- 4H31
- Structural Rating
- 183
- O&M Index
- 2
- O&M Quick
- 2H00
- O&M Rating
- 92
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 275
Pipe schematic from manhole B 0736 to B 0735 Observation photos (3)

3.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

6.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

204.3 ft. - Fracture Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES