Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 5, 2019, 10:59 AM
  • B 0728_B 0727 _05082019_041620.mp4

Date
08/05/2019
W/O
776985
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00111
PipeID
P09192
Time
3:59 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6732
Sewer Name
B JOINT OUTFALL B - UNIT 8H
City
DUARTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_776985_TV22165_JUL2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
B 0728
Downstream MH
B 0727
Dir. of Survey
Downstream
Length Surveyed
290.6 ft.
Total Length
290.6 ft.
Structural Index
3
Structural Quick
513J
Structural Rating
173
O&M Index
2
O&M Quick
2J1C
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
305
Pipe schematic from manhole B 0728 to B 0727
MH: B 0728MH: B 0727downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 07280 ft. MGO - General Observation - CONNECTIONS AT 3 (CAPPED) & 9 O'CLK. (UNKNOWN)0 ft. MWM - Water Mark, 40 %of cross sectional area3.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start18.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start46.1 ft. FS - Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES95.6 ft. FS - Fracture Spiral, from 06 to 09 o'clock, within 8 inches of joint: YES187.9 ft. LR - Alignment Right, 5 %, Start226.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"251.7 ft. RFJ - Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES259.7 ft. FH3 - Fracture Longitudinal Hinge, 3, from 09 to 03 o'clock, within 8 inches of joint: YES271.8 ft. LR - Alignment Right, 5 %, Finish289.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish289.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish290 ft. MGO - General Observation - DAMAGED SHELF @ D/S MH - 9 O'CLK .(CRACKED & POSSIBLE MATERIAL MISSING)290.5 ft. MGO - General Observation - POSSIBLE CONNECTION (UNKNOWN) @ D/S MH - 3 O'CLK.290.6 ft. AMH - Downstream Manhole, Survey Ends - B 0727

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES

    46.1 ft. - Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 06 to 09 o'clock, within 8 inches of joint: YES

    95.6 ft. - Fracture Spiral, from 06 to 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES

    251.7 ft. - Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal Hinge, 3, from 09 to 03 o'clock, within 8 inches of joint: YES

    259.7 ft. - Fracture Longitudinal Hinge, 3, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
0MWL
289.4CM
187.9LR
290.6AMHB 0727
0AMHB 0728
289.5DAGS
226.2TFC
259.7FH3
95.6FS
46.1FS
0MGOCONNECTIONS AT 3 (CAPPED) & 9 O'CLK. (UNKNOWN)
18.5CM
271.8LR
251.7RFJ
290.5MGOPOSSIBLE CONNECTION (UNKNOWN) @ D/S MH - 3 O'CLK.
290MGODAMAGED SHELF @ D/S MH - 9 O'CLK .(CRACKED & POSSIBLE MATERIAL MISSING)
0MWM
3.2DAGS

Properties (6)

additional_info
SC378231
custom_field_two
2
customer
LACSD
datetime
2019-08-05T03:59:14-07:00
documentation
PROPIPE
is_lateral_inspection
false