Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2019, 08:37 AM
  • 08 0369_08 0368 _10082019_084938.mp4

Date
08/13/2019
W/O
782187
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00003
PipeID
P00421
Time
1:37 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6744
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_782187_TV08001_AUG2019_1
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0369
Downstream MH
08 0368
Dir. of Survey
Downstream
Length Surveyed
141.4 ft.
Total Length
141.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 08 0369 to 08 0368
MH: 08 0369MH: 08 0368downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 03692.1 ft. MGO - General Observation - LINED PIPE42.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"127.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"127.8 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start138.8 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish141.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0368141.4 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK CAPPED

Observations (11)

DistanceCodeObservation
0MWM
127.8TB
2.1MGOLINED PIPE
127.8DSC
138.8DSC
0MGOCONNECTION AT MH, 9 O'CLOCK
141.4AMH08 0368
42.8TB
0MWL
0AMH08 0369
141.4MGOCONNECTION AT MH, 9 O'CLOCK CAPPED

Properties (6)

additional_info
SC378243
custom_field_two
4
customer
LACSD
datetime
2019-08-13T01:37:00-07:00
documentation
PROPIPE
is_lateral_inspection
false