Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 10, 2019, 04:50 AM
  • 08 0364_08 0363 _10092019_221744.mp4

Date
10/09/2019
W/O
782187
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00003
PipeID
P00416
Time
9:50 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7058
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_782187_TV08001_AUG2019_1
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0364
Downstream MH
08 0363
Dir. of Survey
Downstream
Length Surveyed
141.5 ft.
Total Length
141.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2B00
O&M Rating
28
Overall Index
2
Overall Quick
Overall Rating
28
Pipe schematic from manhole 08 0364 to 08 0363
MH: 08 0364MH: 08 0363downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 03640 ft. MGO - General Observation - CONNECTION AT 9 O'CLOCK0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area4.5 ft. MGO - General Observation - LINED PIPE4.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start12.4 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"37.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"76.1 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start97 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"139.2 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish139.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish141.5 ft. AMH - Downstream Manhole, Survey Ends - 08 0363141.5 ft. MGO - General Observation - CONNECTION AT 9 O'CLOCK

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
76.1DSC
4.5MGOLINED PIPE
37.8TB
139.2DSC
12.4TBA
139.2DAGS
0AMH08 0364
4.5DAGS
141.5AMH08 0363
0MGOCONNECTION AT 9 O'CLOCK
0MWM
97TB
141.5MGOCONNECTION AT 9 O'CLOCK
0MWL

Properties (6)

additional_info
SC378658
custom_field_two
4
customer
LACSD
datetime
2019-10-09T21:50:15-07:00
documentation
PROPIPE
is_lateral_inspection
false