Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2019, 10:21 AM
  • 08 0362_08 0361 _10082019_092652.mp4

Date
08/13/2019
W/O
782187
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00003
PipeID
P00414
Time
3:21 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6744
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_782187_TV08001_AUG2019_1
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0362
Downstream MH
08 0361
Dir. of Survey
Downstream
Length Surveyed
143.8 ft.
Total Length
143.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 08 0362 to 08 0361
MH: 08 0362MH: 08 0361downstream0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK CAPPED0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 03620 ft. MWM - Water Mark, 40 %of cross sectional area2.1 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - LINED PIPE33.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"33.8 ft. MGO - General Observation - LIGHT STEAM IN SEWER91.4 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"140.3 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish143.8 ft. AMH - Downstream Manhole, Survey Ends - 08 0361143.8 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK

Observations (12)

DistanceCodeObservation
33.8TB
0MGOCONNECTION AT MH, 9 O'CLOCK CAPPED
91.4TB
0MWL
0AMH08 0362
143.8AMH08 0361
0MWM
140.3DSC
33.8MGOLIGHT STEAM IN SEWER
2.1DSC
143.8MGOCONNECTION AT MH, 9 O'CLOCK
2.1MGOLINED PIPE

Properties (6)

additional_info
SC378243
custom_field_two
4
customer
LACSD
datetime
2019-08-13T03:21:00-07:00
documentation
PROPIPE
is_lateral_inspection
false