Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 22, 2019, 10:15 AM
  • 08 0346_08 DAVIDS_10092019_030306.mp4

Date
08/22/2019
W/O
782187
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00003
PipeID
P23452
Time
3:15 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6910
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
15
Purpose
Routine Assessment
Project
RFIR_WO_782187_TV08001_AUG2019_1
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
08 0346
Downstream MH
08 DAVIDS
Dir. of Survey
Downstream
Length Surveyed
326.3 ft.
Total Length
326.3 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 08 0346 to 08 DAVIDS
MH: 08 0346MH: 08 DAVIDSdownstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 08 03462.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start7.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9 ft. MGO - General Observation - LIGHT STEAM IN SEWER11.3 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start264.5 ft. MGO - General Observation - LIGHT STEAM IN SEWER326.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.2 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish326.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish326.2 ft. MGO - General Observation - ABANDONED MH326.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.3 ft. AMH - Downstream Manhole, Survey Ends - 08 DAVIDS

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ABANDONED MH

    326.2 ft. - General Observation - ABANDONED MH

Observations (16)

DistanceCodeObservation
326.2SAP
326.2DSC
2.8SAP
264.5MGOLIGHT STEAM IN SEWER
2.8DAGS
326.2DAGS
0MWM
326.2MGOABANDONED MH
0MWL
326.2SSS
326.3AMH08 DAVIDS
9MGOLIGHT STEAM IN SEWER
0MGOCONNECTION AT MH, 9 O'CLOCK
0AMH08 0346
7.3SSS
11.3DSC

Properties (6)

additional_info
SC378507
custom_field_two
3
customer
LACSD
datetime
2019-08-22T03:15:00-07:00
documentation
PROPIE
is_lateral_inspection
false