Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 22, 2019, 11:02 AM
  • 03 0320_03 0319_10222019_042201.mp4

Date
10/22/2019
W/O
0792616
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00359
PipeID
P04894
Time
4:02 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1282
Sewer Name
03 ANAHEIM STREET TRUNK
City
ANAHEIM
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Routine Assessment
Project
20191017MDM_ANAHEIM_STREET_TRUNK
Material
NRCP
Shape
Circular
Height
30 in.
Upstream MH
03 0320
Downstream MH
03 0319
Dir. of Survey
Downstream
Length Surveyed
330.8 ft.
Total Length
330.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole 03 0320 to 03 0319
MH: 03 0320MH: 03 0319downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:30AM2 ft. MGO - General Observation - 30" NRCP-CIPP2 ft. MGO - General Observation - WHITE BUILDUP ON PIPE60.7 ft. LFZ - Lining Failure Other, from 08 to 04 o'clock, within 8 inches of joint: NO, Start - POSSIBLE CORRODING OR THICK WHITE BUILDUP60.7 ft. LFZ - Lining Failure Other, from 08 to 04 o'clock, within 8 inches of joint: NO - POSSIBLE CORRODING FIBERS326.8 ft. MGO - General Observation - LOOSE LINER AT MH330.1 ft. LFZ - Lining Failure Other, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish - POSSIBLE FIBER CORROSION OR THICK BUILDUP ON LINER330.8 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (5)

  • General Observation - 30" NRCP-CIPP

    2 ft. - General Observation - 30" NRCP-CIPP

  • General Observation - WHITE BUILDUP ON PIPE

    2 ft. - General Observation - WHITE BUILDUP ON PIPE

  • Lining Failure Other, from 08 to 04 o'clock, within 8 inches of joint: NO, Start - POSSIBLE CORRODING OR THICK WHITE BUILDUP

    60.7 ft. - Lining Failure Other, from 08 to 04 o'clock, within 8 inches of joint: NO, Start - POSSIBLE CORRODING OR THICK WHITE BUILDUP

  • Lining Failure Other, from 08 to 04 o'clock, within 8 inches of joint: NO - POSSIBLE CORRODING FIBERS

    60.7 ft. - Lining Failure Other, from 08 to 04 o'clock, within 8 inches of joint: NO - POSSIBLE CORRODING FIBERS

  • General Observation - LOOSE LINER AT MH

    326.8 ft. - General Observation - LOOSE LINER AT MH

Observations (10)

DistanceCodeObservation
60.7LFZPOSSIBLE CORRODING OR THICK WHITE BUILDUP
2MGO30" NRCP-CIPP
60.7LFZPOSSIBLE CORRODING FIBERS
326.8MGOLOOSE LINER AT MH
0MWM
0MWL
2MGOWHITE BUILDUP ON PIPE
330.1LFZPOSSIBLE FIBER CORROSION OR THICK BUILDUP ON LINER
0AMH4:30AM
330.8AMH5:00AM

Properties (7)

custom_field_three
POSSIBLE LINER CORROSION
custom_field_two
4
customer
LACSD
datetime
2019-10-22T04:02:55-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false
lining
CIPP