Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 23, 2019, 03:52 PM
  • G 0315_G 0314_10232019_100955.mp4

Date
10/23/2019
W/O
0792773
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00228
PipeID
P01751
Time
8:52 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8109
Sewer Name
01 WRIGHT ROAD TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Capital Improvement Program Assesment
Project
20191018DF_JOINT_OUTFALL_G_UNIT_9_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
G 0315
Downstream MH
G 0314
Dir. of Survey
Downstream
Length Surveyed
309.6 ft.
Total Length
309.6 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
18
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
21
Pipe schematic from manhole G 0315 to G 0314
MH: G 0315MH: G 0314downstream0 ft. AMH - Upstream Manhole, Survey Begins - 8:56 AM0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.9 ft. MGP - General Photograph111.2 ft. MGP - General Photograph189.6 ft. MGP - General Photograph230 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start273.1 ft. MGP - General Photograph304.2 ft. MGP - General Photograph307.3 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 65% MAG307.3 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish307.3 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish307.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish307.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish307.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish307.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309.6 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)309.6 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - @ MH309.6 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach309.6 ft. AMH - Downstream Manhole, Survey Ends - 10:35 AM

Observation photos (13)

  • Upstream Manhole, Survey Begins - 8:56 AM

    0 ft. - Upstream Manhole, Survey Begins - 8:56 AM

  • Deposits Attached Ragging, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Ragging, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    28.9 ft. - General Photograph

  • General Photograph

    111.2 ft. - General Photograph

  • General Photograph

    189.6 ft. - General Photograph

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    230 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    273.1 ft. - General Photograph

  • General Photograph

    304.2 ft. - General Photograph

Observations (26)

DistanceCodeObservation
309.6MGOGREASE THROUGHOUT THE REACH (5%)
2DAR
304.2MGP
0AMH8:56 AM
309.6VC@ MH
307.3SZ65% MAG
307.3SRC
2SRC
2SZ65% MAG
189.6MGP
28.9MGP
2SAP
307.3DAR
307.3CM
309.6MGOPeeling & Flaking Throughout The Reach
307.3SSS
2SSS
111.2MGP
307.3SAP
2CM
0MWL
0MWM
230SRV
309.6AMH10:35 AM
307.3SRV
273.1MGP

Properties (6)

custom_field_three
MISSING TILES/AGGREGATE PROJECTING
custom_field_two
2
customer
LACSD
datetime
2019-10-23T08:52:00-07:00
documentation
FRANKLIN, RUVALCABA, IGNACIO, BRAR
is_lateral_inspection
false