Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 22, 2019, 05:11 PM
  • G 0316_G 0315_10222019_120230.mp4

Date
10/22/2019
W/O
0792773
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00228
PipeID
P01752
Time
10:11 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8108
Sewer Name
01 WRIGHT ROAD TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Capital Improvement Program Assesment
Project
20191018DF_JOINT_OUTFALL_G_UNIT_9_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
G 0316
Downstream MH
G 0315
Dir. of Survey
Downstream
Length Surveyed
195 ft.
Total Length
195 ft.
Structural Index
3
Structural Quick
5132
Structural Rating
13
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole G 0316 to G 0315
MH: G 0316MH: G 0315downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:00 PM0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - @ MH2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26.7 ft. MGP - General Photograph29.1 ft. MGP - General Photograph89.3 ft. MGP - General Photograph99.8 ft. MGP - General Photograph125.1 ft. MGP - General Photograph125.1 ft. MGP - General Photograph145.5 ft. MGP - General Photograph192.6 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - @ MH193.2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 65% MAG193.7 ft. MGO - General Observation - Grease Throughout The Reach (5%)193.8 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish194.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish194.3 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach194.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish194.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish195 ft. AMH - Downstream Manhole, Survey Ends - 12:23 PM

Observation photos (13)

  • Upstream Manhole, Survey Begins - 12:00 PM

    0 ft. - Upstream Manhole, Survey Begins - 12:00 PM

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    26.7 ft. - General Photograph

  • General Photograph

    29.1 ft. - General Photograph

  • General Photograph

    89.3 ft. - General Photograph

  • General Photograph

    99.8 ft. - General Photograph

  • General Photograph

    125.1 ft. - General Photograph

  • General Photograph

    125.1 ft. - General Photograph

  • General Photograph

    145.5 ft. - General Photograph

Observations (25)

DistanceCodeObservation
2SZ65% MAG
194.2SAP
99.8MGP
26.7MGP
193.7MGOGrease Throughout The Reach (5%)
0MWM
193.2SZ65% MAG
125.1MGP
2SAP
2SRC
125.1MGP
2SSS
194.4CM
2VC@ MH
192.6VC@ MH
29.1MGP
0AMH12:00 PM
2CM
194.3MGOPeeling & Flaking Throughout The Reach
193.8SRC
195AMH12:23 PM
0MWL
194.7SSS
89.3MGP
145.5MGP

Properties (7)

additional_info
PIPE ID ONSCREEN IS WRONG. CORRECT PIPE ID IS (P01752)
custom_field_three
MISSING TILES/AGGREGATE PROJECTING
custom_field_two
2
customer
LACSD
datetime
2019-10-22T10:11:43-07:00
documentation
FRANKLIN, RUVALCABA, IGNACIO, BRAR
is_lateral_inspection
false