Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 22, 2019, 06:25 PM
  • G 0318_G 0317_10222019_112710.mp4

Date
10/22/2019
W/O
0792773
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00228
PipeID
P01754
Time
11:25 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8108
Sewer Name
01 WRIGHT ROAD TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Capital Improvement Program Assesment
Project
20191018DF_JOINT_OUTFALL_G_UNIT_9_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
G 0318
Downstream MH
G 0317
Dir. of Survey
Downstream
Length Surveyed
96.7 ft.
Total Length
96.7 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
18
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole G 0318 to G 0317
MH: G 0318MH: G 0317downstream0 ft. AMH - Upstream Manhole, Survey Begins - 11:25 AM0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - Conn. @ Mh, 5 O' Clock. Active2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start73 ft. MGP - General Photograph79.8 ft. MGP - General Photograph94 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish94 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish94 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish94 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish94 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 65% MAG94 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish96.7 ft. MGO - General Observation - Conn. @ Mh, 8 O' Clock. UNKNOWN96.7 ft. AMH - Downstream Manhole, Survey Ends - 11:42 AM96.7 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active96.7 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - @ MH96.7 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach96.7 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)

Observation photos (9)

  • Upstream Manhole, Survey Begins - 11:25 AM

    0 ft. - Upstream Manhole, Survey Begins - 11:25 AM

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    73 ft. - General Photograph

  • General Photograph

    79.8 ft. - General Photograph

Observations (25)

DistanceCodeObservation
79.8MGP
2SRV
94SSS
2MGOConn. @ Mh, 3 O' Clock. Active
2CM
2SZ65% MAG
94SRV
96.7MGOConn. @ Mh, 8 O' Clock. UNKNOWN
2SSS
94SAP
0AMH11:25 AM
73MGP
96.7AMH11:42 AM
96.7MGOConn. @ Mh, 9 O' Clock. Active
2MGOConn. @ Mh, 5 O' Clock. Active
2SRC
2SAP
96.7VC@ MH
94CM
94SZ65% MAG
0MWL
0MWM
96.7MGOPeeling & Flaking Throughout The Reach
96.7MGOGREASE THROUGHOUT THE REACH (5%)
94SRC

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-10-22T11:25:08-07:00
documentation
FRANKLIN, RUVALCABA, IGNACIO, BRAR
is_lateral_inspection
false