Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 22, 2019, 03:53 PM
  • G 0319_G 0318_10222019_104822.mp4

Date
10/22/2019
W/O
0792773
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00228
PipeID
P01755
Time
8:53 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8108
Sewer Name
01 WRIGHT ROAD TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Capital Improvement Program Assesment
Project
20191018DF_JOINT_OUTFALL_G_UNIT_9_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
G 0319
Downstream MH
G 0318
Dir. of Survey
Downstream
Length Surveyed
462.3 ft.
Total Length
462.3 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
18
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
18
Pipe schematic from manhole G 0319 to G 0318
MH: G 0319MH: G 0318downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 10:12 AM0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 60% MAG2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.8 ft. MGP - General Photograph35.3 ft. MGP - General Photograph48.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start76.5 ft. MGP - General Photograph142.9 ft. MGP - General Photograph300.1 ft. MGP - General Photograph344.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start458.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish458.9 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish458.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish458.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish458.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish458.9 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 65% MAG462.3 ft. MGO - General Observation - Conn. @ Mh, 5 O' Clock. Active462.3 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach462.3 ft. AMH - Downstream Manhole, Survey Ends - 11:23 AM462.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active462.3 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)

Observation photos (11)

  • Upstream Manhole, Survey Begins - 10:12 AM

    0 ft. - Upstream Manhole, Survey Begins - 10:12 AM

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    22.8 ft. - General Photograph

  • General Photograph

    35.3 ft. - General Photograph

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    48.1 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    76.5 ft. - General Photograph

  • General Photograph

    142.9 ft. - General Photograph

  • General Photograph

    300.1 ft. - General Photograph

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    344.5 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (25)

DistanceCodeObservation
458.9SSS
2CM
458.9SRC
142.9MGP
344.5SRV
458.9CM
0MWL
48.1SRC
458.9SAP
462.3MGOConn. @ Mh, 5 O' Clock. Active
458.9SRV
76.5MGP
2SZ60% MAG
22.8MGP
35.3MGP
458.9SZ65% MAG
2SAP
462.3MGOPeeling & Flaking Throughout The Reach
462.3AMH11:23 AM
0AMH10:12 AM
300.1MGP
462.3MGOConn. @ Mh, 3 O' Clock. Active
2SSS
462.3MGOGREASE THROUGHOUT THE REACH (5%)
0MWM

Properties (6)

custom_field_three
TILES MISSING/AGGREGATE PROJECTING
custom_field_two
2
customer
LACSD
datetime
2019-10-22T08:53:16-07:00
documentation
FRANKLIN, RUVALCABA, IGNACIO, BRAR
is_lateral_inspection
false