Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 21, 2019, 03:38 PM
  • G 0320_G 0319_10212019_113159.mp4

Date
10/21/2019
W/O
0792773
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00228
PipeID
P01756
Time
8:38 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8107
Sewer Name
01 WRIGHT ROAD TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Capital Improvement Program Assesment
Project
20191018DF_JOINT_OUTFALL_G_UNIT_9_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
G 0320
Downstream MH
G 0319
Dir. of Survey
Downstream
Length Surveyed
168 ft.
Total Length
168 ft.
Structural Index
3
Structural Quick
5132
Structural Rating
13
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole G 0320 to G 0319
MH: G 0320MH: G 0319downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 11:29 AM2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active/DROP CONN2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 60% MAG2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - @ MH26 ft. MGP - General Photograph48.2 ft. MGP - General Photograph67.2 ft. MGP - General Photograph135.1 ft. MGP - General Photograph165.5 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)165.7 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach166.4 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 60% MAG167.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish167.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish167.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish168 ft. AMH - Downstream Manhole, Survey Ends - 11:46 AM168 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (9)

  • Upstream Manhole, Survey Begins - 11:29 AM

    0 ft. - Upstream Manhole, Survey Begins - 11:29 AM

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 60% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 60% MAG

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    26 ft. - General Photograph

  • General Photograph

    48.2 ft. - General Photograph

  • General Photograph

    67.2 ft. - General Photograph

  • General Photograph

    135.1 ft. - General Photograph

Observations (23)

DistanceCodeObservation
2CM
2SSS
2MGOConn. @ Mh, 3 O' Clock. Active/DROP CONN
26MGP
48.2MGP
167.9SSS
2MGOConn. @ Mh, 9 O' Clock. Active
168AMH11:46 AM
2SZ60% MAG
135.1MGP
167.5SAP
2SAP
67.2MGP
168CM
0MWM
166.4SZ60% MAG
2SRV
165.5MGOGREASE THROUGHOUT THE REACH (5%)
0MWL
167.2SRV
0AMH11:29 AM
2VC@ MH
165.7MGOPeeling & Flaking Throughout The Reach

Properties (6)

custom_field_three
MISSING TILES/AGGREGATE PROJECTING
custom_field_two
2
customer
LACSD
datetime
2019-10-21T08:38:06-07:00
documentation
FRANKLIN, RUVALCABA, IGNACIO, SHADLER
is_lateral_inspection
false