Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 15, 2019, 09:43 PM
  • 28 0083_28 0082_10152019_144607.mp4

Date
10/15/2019
W/O
PENDING
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00912
PipeID
P21838
Time
2:43 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8102
Sewer Name
28 FOOTHILL BOULEVARD MAIN TRUNK
City
LA CANADA FLINTRIDGE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 28
Page No.
01
Purpose
Maintenance Related
Project
20191015DF_FOOTHILL_BOULEVARD_MAIN_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
28 0083
Downstream MH
28 0082
Dir. of Survey
Downstream
Length Surveyed
212.8 ft.
Total Length
212.8 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 28 0083 to 28 0082
MH: 28 0083MH: 28 0082downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:45 PM0.1 ft. MWM - Water Mark, 30 %of cross sectional area0.1 ft. MWL - Water Level, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open123.6 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 4"132.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open138 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open144.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open209.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish212.8 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)212.8 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active212.8 ft. AMH - Downstream Manhole, Survey Ends - 3:00 PM

Observation photos (2)

  • Upstream Manhole, Survey Begins - 2:45 PM

    0 ft. - Upstream Manhole, Survey Begins - 2:45 PM

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
123.6TFA
0.1MWM
0.1MWL
144.1TBOpen
212.8MGOGREASE THROUGHOUT THE REACH (5%)
0AMH2:45 PM
209.3SSS
212.8MGOConn. @ Mh, 9 O' Clock. Active
132.1TFOpen
212.8AMH3:00 PM
138TFOpen
8.9TFOpen
2SSS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-10-15T14:43:38-07:00
documentation
FRANKLIN, MIRANDA , SHADLER
is_lateral_inspection
false