Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2017, 04:31 PM
  • 02 0959_02 0958_6232017_094928.mp4

Date
06/23/2017
W/O
PENDING
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00279
PipeID
P03528
Time
9:31 AM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7442
Sewer Name
02 MONTEBELLO TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Maintenance Related
Project
20170623MI_MONTEBELLO_TRUNK
Material
NRCP
Shape
Circular
Height
21 in.
Upstream MH
02 0959
Downstream MH
02 0958
Dir. of Survey
Downstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 02 0959 to 02 0958
MH: 02 0959MH: 02 0958downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - MAG INSPECTION ONLY0 ft. AMH - Upstream Manhole, Survey Begins - 09:50 AM2 ft. DSZ - Deposits Settled Other, 25 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - MAGNESIUM HYDROXIDE2 ft. MSA - Survey Abandoned - DUE TO MAG DEPOSITS, FROM 4 TO 8 OCLOCK, 25%

Observation photos (2)

  • Deposits Settled Other,  25 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES - MAGNESIUM HYDROXIDE

    2 ft. - Deposits Settled Other, 25 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - MAGNESIUM HYDROXIDE

  • Survey Abandoned - DUE TO MAG DEPOSITS, FROM 4 TO 8 OCLOCK, 25%

    2 ft. - Survey Abandoned - DUE TO MAG DEPOSITS, FROM 4 TO 8 OCLOCK, 25%

Observations (6)

DistanceCodeObservation
2DSZMAGNESIUM HYDROXIDE
0MWM
0MWL
0MGOMAG INSPECTION ONLY
2MSADUE TO MAG DEPOSITS, FROM 4 TO 8 OCLOCK, 25%
0AMH09:50 AM

Properties (6)

additional_info
MAG INSPECTION ONLY
custom_field_two
5
customer
LACSD
datetime
2017-06-23T09:31:15-07:00
documentation
IGNACIO, FRANKLIN, BRAR
is_lateral_inspection
false