Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2017, 11:39 AM
  • 01 1101_01 1100_262017_034130.mp4

Date
02/06/2017
W/O
0613635
Weather
Heavy Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00210
PipeID
P01951
Time
3:39 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0431
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20170206MDM_HUNTINGTON_PARK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 1101
Downstream MH
01 1100
Dir. of Survey
Downstream
Length Surveyed
299.8 ft.
Total Length
299.8 ft.
Structural Index
3
Structural Quick
3625
Structural Rating
28
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
32
Pipe schematic from manhole 01 1101 to 01 1100
MH: 01 1101MH: 01 1100downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:40AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN47.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active61.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE86.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open103.5 ft. MGO - General Observation - 18" VCP113.2 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H124.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open127 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT137.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open141.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE146.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT146.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H154.6 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SLIGHT162.3 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H183.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT193.8 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H206.7 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - SL210.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open213.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H238.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open266.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H273.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6", 6" - Active285.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open299.8 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observation photos (3)

  • General Observation - 18" VCP

    103.5 ft. - General Observation - 18" VCP

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    141.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    146.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

Observations (27)

DistanceCodeObservation
0MWM
162.3FCH
183.3FLSLIGHT
266.2FLH
210.7TFOpen
285.2TFOpen
0MWL
86.3TFOpen
238.7TFOpen
127FCSLIGHT
193.8FCH
273.9TFActive
0AMH3:40AM
141.4FLHAIRLINE
146.2FLSLIGHT
61.7FLHAIRLINE
47.4TFActive
113.2FLH
137.5TFOpen
124.9TFOpen
213.5FLH
0MGOConn. @ Mh, 3 O' Clock. OPEN
299.8AMH4:25AM
206.7FCSL
103.5MGO18" VCP
146.2FLH
154.6FCSLIGHT

Properties (6)

custom_field_three
SLIGHT LONG FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2017-02-06T03:39:41-08:00
documentation
MARTIN,MANANES,REVELES
is_lateral_inspection
false