Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2017, 09:42 PM
  • B 0237_B 0236_262017_135233.mp4

Date
02/06/2017
W/O
PENDING
Weather
Light Rain
Operator/Surveyor
MIRANDA
Sewer ID
Z00077
PipeID
P08705
Time
1:42 PM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7324
Sewer Name
B JOINT OUTFALL B - UNIT 1E
City
MONTEBELLO
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
11
Purpose
Maintenance Related
Project
20170206AM_JOINT_OUTFALL_B_UNIT_1E
Material
NRCP
Shape
Circular
Height
21 in.
Upstream MH
B 0237
Downstream MH
B 0236
Dir. of Survey
Downstream
Length Surveyed
32 ft.
Total Length
32 ft.
Structural Index
5
Structural Quick
5300
Structural Rating
15
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
15
Pipe schematic from manhole B 0237 to B 0236
MH: B 0237MH: B 0236downstream0 ft. MWL - Water Level, 5 %of cross sectional area - STAGNANT WATER0 ft. AMH - Upstream Manhole, Survey Begins - 1:52 PM9 ft. SMW - Surface Missing Wall, from 10 to 01 o'clock, within 8 inches of joint: YES - SOIL/VOID VISIBLE12 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL/VOID VISIBLE15 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL/VOID VISIBLE31 ft. MWL - Water Level, 45 %of cross sectional area32 ft. MSA - Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

Observation photos (7)

  • Water Level, 5 %of cross sectional area - STAGNANT WATER

    0 ft. - Water Level, 5 %of cross sectional area - STAGNANT WATER

  • Upstream Manhole, Survey Begins - 1:52 PM

    0 ft. - Upstream Manhole, Survey Begins - 1:52 PM

  • Surface Missing Wall, from 10 to 01 o'clock, within 8 inches of joint: YES - SOIL/VOID VISIBLE

    9 ft. - Surface Missing Wall, from 10 to 01 o'clock, within 8 inches of joint: YES - SOIL/VOID VISIBLE

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL/VOID VISIBLE

    12 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL/VOID VISIBLE

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL/VOID VISIBLE

    15 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL/VOID VISIBLE

  • Water Level, 45 %of cross sectional area

    31 ft. - Water Level, 45 %of cross sectional area

  • Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

    32 ft. - Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

Observations (7)

DistanceCodeObservation
32MSAVIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
0MWLSTAGNANT WATER
9SMWSOIL/VOID VISIBLE
31MWL
0AMH1:52 PM
12SMWSOIL/VOID VISIBLE
15SMWSOIL/VOID VISIBLE

Properties (7)

additional_info
EMERGENCY INSPECTION, SINKHOLE, VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
custom_field_three
3 MISSING WALLS WITH SOIL/VOID VISIBLE
custom_field_two
1
customer
LACSD
datetime
2017-02-06T13:42:36-08:00
documentation
MIRANDA, BRAR, SHADLER, IGNACIO
is_lateral_inspection
false